RM Series 100-600kVA Modular Online UPS(380V/400V/415V)

This series Modular UPS is equipped with hot-swappable power module and bypass & monitoring modules, which are designed for easy maintenance and redundancy. 100kVA power capacity in a 4U-high module, combined with a bypass module that is integrated with various communication ports.

Email Us
  • Product description
  • Features
  • Specifications
  • Application Case
  • Download
    • Commodity name: RM Series 100-600kVA Modular Online UPS(380V/400V/415V)
    • Commodity ID: 1063515906429833216

    This series Modular UPS is equipped with hot-swappable power module and bypass & monitoring modules, which are designed for easy maintenance and redundancy. 100kVA power capacity in a 4U-high module, combined with a bypass module that is integrated with various communication ports.

    The modular online UPS, single cabinet power rating covers from 100kVA to 600kVA, provides the highest power density of 100kW power modules in 4U height, 4 units can be paralleled for capacity maximum up to 3.2MW.  With the patent of Battery Neutral Free design, the RM series deliver the best combination of reliability, hot swappable and flexibility.

  • Low-carbon & Green

    This series 3 level inverter, fully digital control. Achieving the input power factor ≥0.99, input THDi ≤3%, leading overall efficiency up to 96%.

     

    Wide Range of the battery number

    Support 30-48 pcs batteries (settable).
    Shared battery pack in parallel UPS system.                                               
    Support Lithium battery.
    Battery N line free patent.

    Saving power distribution switch and instruction cost. Therefore, it becomes more flexible for customer.

     

    High Power Density

    The 600kW system can reach to 3.2MW.
    Power module: the single module power density 100kW/4U.
    Meet the large data center application site.

     

    LCD screen with IOT & intelligent monitoring

    10-inch color touch screen with new display style. 
    Support IOT and intelligent data monitoring.
    Provide users intuitive display while reducing human fault.
    Record maximum 2000 history logs.

     

    All-round intelligent detection

    Monitoring the operating status of critical component, able to set early warning.
    Record the rectifier/inverter abnormal info of the power module and catch the waveform which can be exported to computer by USB.

     

    High system capacity up to 3.2MW

    Power Module
    There are 6 slots for power modules, easily achieve module redundancy.

     

    UPS Parallel
    Parallel Unit maximum: 4 cabinets.
    Total capacity reach to 3.2MW.

     

    Standard Cabinet
    There are 5/6/8 slots UPS standard cabinets.

  • Model RM600/100D
    System Capacity 600kVA
    Power Module Capacity 100kVA/100kW
    Input Dual Input Optinal
    Phase 3Phase+Neutral+Ground, 380/400/415VAC (line-line)
    Rate Frequency 50/60Hz
    Input Voltage Range 323~478Vac (line-line), full load; 323V~191Vac (line-line), load decrease linearly from 100%~40%; 191V~138V (line-line), load decrease linearly from 45%~35% according to the min phase voltage
    Input Frequency Range 40Hz70Hz
    Input PF >0.99
    Input THDi <3% (100% Linear load)
    Bypass Rate Voltage 380/400/415VAC  (line-line)
    Rate Frequency 50/60Hz
    Input voltage Range Settable, default -20% ~ +15%
    Up limit: +10%, +15%, +20%, +25%
    Down limit: -10%, -15%, -20%, -30%, -40%
    Bypass Frequency Range Settable, ±1Hz, ±3Hz, ±5Hz
    Bypass Overload 110% long term operation; 110% ~ 125% for 5 mins; 125% ~ 150% for 1 min;
    150% ~ 400% for 1 s; >400%  less than 200ms
    Output Rate Voltage 380/400/415VAC  (line-line)
    Rate Frequency 50/60Hz
    Output PF 1
    Voltage Regulation ±1%
    Output THDu <1% , Linear load, <5% , Non-linear load
    Inverter Overload <110% for 1 hour; 110%~125% for 10 mins;
    125%~150% for 1 min; >150% for 200ms
    Frequency Precision ±0.1%
    Battery Voltage ±180 ~ 288VDC
    30 ~ 32pcs derate to 0.7
    34 ~ 36pcs derate to 0.8
          38pcs derate to 0.9
    40 ~ 48pcs
    Voltage Precision ±1%
    Charge Power Up to 15% * Output active power
    System Efficiency AC Mode >96%
    Battery Mode >95%
    Display LED+ Color touch LCD screen
    Interface RS485, USB, CAN, Programmable Dry Contact, 2 Intelligent slots
    Option SNMP Card, AS400 Card, Parallel kit, dual input kit, SPD, LBS, GSM
    Temperature Operation: 0 ~ 40 ℃  Storge: -40~70
    Relative Humidity 0 ~ 95% Non-condensing
    Noise (1 meter) 75dB @ 100% load, 70dB @ 45% load
    Altitude <1000m. Within 1000~2000m, 1% power derating for every 100m rise
    Physical Dimension
    (W*D*H,mm)
    Cabinet 1000*1100*2000
    Power module 440*794.5*174
    Weight (kg) Cabinet 500
    Power module 50

Features

Specifications

Application Case

Download

Low-carbon & Green

This series 3 level inverter, fully digital control. Achieving the input power factor ≥0.99, input THDi ≤3%, leading overall efficiency up to 96%.

 

Wide Range of the battery number

Support 30-48 pcs batteries (settable).
Shared battery pack in parallel UPS system.                                               
Support Lithium battery.
Battery N line free patent.

Saving power distribution switch and instruction cost. Therefore, it becomes more flexible for customer.

 

High Power Density

The 600kW system can reach to 3.2MW.
Power module: the single module power density 100kW/4U.
Meet the large data center application site.

 

LCD screen with IOT & intelligent monitoring

10-inch color touch screen with new display style. 
Support IOT and intelligent data monitoring.
Provide users intuitive display while reducing human fault.
Record maximum 2000 history logs.

 

All-round intelligent detection

Monitoring the operating status of critical component, able to set early warning.
Record the rectifier/inverter abnormal info of the power module and catch the waveform which can be exported to computer by USB.

 

High system capacity up to 3.2MW

Power Module
There are 6 slots for power modules, easily achieve module redundancy.

 

UPS Parallel
Parallel Unit maximum: 4 cabinets.
Total capacity reach to 3.2MW.

 

Standard Cabinet
There are 5/6/8 slots UPS standard cabinets.

Model RM600/100D
System Capacity 600kVA
Power Module Capacity 100kVA/100kW
Input Dual Input Optinal
Phase 3Phase+Neutral+Ground, 380/400/415VAC (line-line)
Rate Frequency 50/60Hz
Input Voltage Range 323~478Vac (line-line), full load; 323V~191Vac (line-line), load decrease linearly from 100%~40%; 191V~138V (line-line), load decrease linearly from 45%~35% according to the min phase voltage
Input Frequency Range 40Hz70Hz
Input PF >0.99
Input THDi <3% (100% Linear load)
Bypass Rate Voltage 380/400/415VAC  (line-line)
Rate Frequency 50/60Hz
Input voltage Range Settable, default -20% ~ +15%
Up limit: +10%, +15%, +20%, +25%
Down limit: -10%, -15%, -20%, -30%, -40%
Bypass Frequency Range Settable, ±1Hz, ±3Hz, ±5Hz
Bypass Overload 110% long term operation; 110% ~ 125% for 5 mins; 125% ~ 150% for 1 min;
150% ~ 400% for 1 s; >400%  less than 200ms
Output Rate Voltage 380/400/415VAC  (line-line)
Rate Frequency 50/60Hz
Output PF 1
Voltage Regulation ±1%
Output THDu <1% , Linear load, <5% , Non-linear load
Inverter Overload <110% for 1 hour; 110%~125% for 10 mins;
125%~150% for 1 min; >150% for 200ms
Frequency Precision ±0.1%
Battery Voltage ±180 ~ 288VDC
30 ~ 32pcs derate to 0.7
34 ~ 36pcs derate to 0.8
      38pcs derate to 0.9
40 ~ 48pcs
Voltage Precision ±1%
Charge Power Up to 15% * Output active power
System Efficiency AC Mode >96%
Battery Mode >95%
Display LED+ Color touch LCD screen
Interface RS485, USB, CAN, Programmable Dry Contact, 2 Intelligent slots
Option SNMP Card, AS400 Card, Parallel kit, dual input kit, SPD, LBS, GSM
Temperature Operation: 0 ~ 40 ℃  Storge: -40~70
Relative Humidity 0 ~ 95% Non-condensing
Noise (1 meter) 75dB @ 100% load, 70dB @ 45% load
Altitude <1000m. Within 1000~2000m, 1% power derating for every 100m rise
Physical Dimension
(W*D*H,mm)
Cabinet 1000*1100*2000
Power module 440*794.5*174
Weight (kg) Cabinet 500
Power module 50

Related Application Cases

Related Products

RM Series 60-600kVA Modular Online UPS (380V/400V/415V)

60-600kVA modular online UPS with brand-new topology, a bidirectional DC-DC converter circuit, which greatly improves the system's performance and guarantees high efficiency. Its compact design ensures the power density, achieve this 600kW system occupies only an area of 0.9m2 . RM series is considered to be an excellent power supply solution for large data centers and facilities.

RM Series Rack-Mounted Modular Online UPS 5-20kVA (380V/400V/415V)

It's a single-phase modular UPS that can be configured with up to 6 power modules(maximum 20kVA), 5 groups of battery modules, and optional 10A charging module. It can be flexible configured to 1 phase in and out without deration to satisfy various projects requirements, compatible with all kinds of 19” standard sever cabinet. The whole product is a complete tower modular UPS system, especially suitable for small and medium server rooms.

RM Series Modular Online UPS 40-600kVA (380V/400V/415V)

The series Modular Online UPS is cost-beneficial product for medium and large data center. 50kVA power module in 4U height, 600kVA in one cabinet and the footprint less than 1.45m2, 3 units in parallel for a capacity up to 1500kVA. It provides 80kVA, 100kVA, 160kVA, 200kVA, 240kVA, 300kVA, 400kVA, 500kVA, 600kVA for choosing.

RM Series Modular Online UPS 25-600kVA (380V/400V/415V)

The series Modular Online UPS is high reliability and adaptability product for medium and large data center. The series is the upgrade of 20 -200 kVA series UPS, and the capacity can be expanded to 900 kVA. It provides 150kVA, 180kVA, 250kVA, 300kVA, 500kVA, 600kVA for choosing. Modular IGBT design and isolated air channel ensured its high impact resistance and the wide adaptability of harsh environment.