HTC11 Series Tower Online UPS 1-3kVA 2.0 (220V/230V/240V)
This series tower UPS is the 2.0 version of HT11 1-3kVA, which is to meet the requirements for energy conservation and emission reduction of the markets, compared with the old one, it has a smaller size, better performance, and more competitive price and quality! its power ranges from 1kVA to 3kVA, This product can be widely used, such as small data centers, bank branches, telecom business halls, office buildings, and various edge computing scenarios. (watch the introduction video on YouTube)
Email Us
- Product description
- Features
- Specifications
- Certification
- Download
-
This series tower UPS is the 2.0 version of HT11 1-3kVA, which is to meet the requirements for energy conservation and emission reduction of the markets, compared with the old one, it has a smaller size, better performance, and more competitive price and quality! its power ranges from 1kVA to 3kVA, This product can be widely used, such as small data centers, bank branches, telecom business halls, office buildings, and various edge computing scenarios. (watch the introduction video on YouTube)
-
● Wide range of input voltage while input PF>0.99
● Output PF of 1, upgraded overload capability
● Full protection of over-voltage and short-circuit
● Multiple communication interface: RS232 RS485AS400, dry contact, USB and SNMP card
● LCD/LED display, monitoring all the operation status
● Auto fan speed adjustment
● External environment and battery temperature sensor
● 1-12A adjustable charger with more flexibility
● Support Lithium battery
-
HT1101CL HT1101CS HT1102CL HT1102CS HT1103CL HT1103CS System Capacity 1kVA 2kVA 3kVA Phase Single Phase in, Single Phase out Battery Cold Start Standard Input Volatge Range 110VAC~300VAC 176VAC~276VAC for 100% load; 276VAC~300VAC for 50% load; 110VAC~176VAC load decrease linearly from 100%~50% Transfer Voltage Range 220/230/240VAC -Line low transfer 110VAC -Line low recovery 120VAC -Line high transfer 300VAC -Line high recovery 290VAC Input Current Rated Current 4.9A 9.7A 14.5A Input Power Factor ≥0.99 THDi <3% (100% Linear load); <5% (non-linear load) Input frequency Range 50/60±5Hz(Default),±1Hz/±3Hz(Optional) Output Frequency adaptable Settable Power Apparent Power(KVA) 1 2 3 Active Power(KW) 1(0.9 for 200VAC/208VAC) 2(1.8 for 200VAC/208VAC) 3(2.7 for 200VAC/208VAC) Output Voltage -Waveform(Bat. Mode) Pure Sine Wave Rated Voltage 220/230/240VAC, 200/208VAC (PF=0.9) -Voltage regulation ± 1 % - Dynamic response ≤5% (0% - 100% -0%) - Dynamic recovery ≤40ms (0% - 100% -0%) - Voltage distortion ≤1% THD,linear load ≤ 5% THD, non-linear load Output Frequency Synchronization range Mains mode: follow the mains frequency,Battery mode: 50/60Hz±0.1% Transfer Time -Line mode to battery mode 0 -Inverter to bypass 2ms Effciency -Line mode with battery full charged 94.5%@100% load 95%@100% load 95.5%@100% load -ECO mode 98.0% -Battery mode 89.5%@100% load 91.5%@100% load 91.5%@100% load Noise(1m away) <43dB@<60%load,<47dB@>60%load <50dB@<60%load,<55dB@>60%load Overload Capability(Inverter) 102%~110%: Transfer to bypass after 30mins 110%~125%: Transfer to bypass after 10mins 125%~150%: Transfer to bypass after 30s Overload Capability(Battery Mode) 102%~110%:Transfer to bypass after 1min 110%~125%: Transfer to bypass after 10s 125%~150%:shutdown after 5s Overload Capability (Bypass Mode) <130%: Long time 130%~150%: shutdown after10mins 150%~180%: shutdown after 5s Crest Factor 3:1 BATTERY Rating/Type Depend on the capacity of external batteries 12VDC/7Ah Depend on the capacity of external batteries 12VDC/7Ah Depend on the capacity of external batteries 12VDC/7Ah Quantity 3 6 8 DC Voltage 36VDC 72VDC 96VDC Back-up Time Depend on the capacity of external batteries 3mins @80% load Depend on the capacity of external batteries 3mins @80% load Depend on the capacity of external batteries 3mins @80% load Battery Charger -Charging Voltage -Charging Current 1-12A(Settable) 1A 1-12A(Settable) 1A 1-12A(Settable) 1A - Charging Time Depend on the capacity of external batteries 8h recharge to 90% Depend on the capacity of external batteries 8h recharge to 90% Depend on the capacity of external batteries 8h recharge to 90% INDICATOR & ALARM -Display LED+LCD -Discharge Sound once every 2 minutes -Low Battery Voltage Sound once every 6s -Battery Overload Continuous beeping -Input Voltage Abnormality(Include Sequential Negative,Ground wire not connected) Sound once every 2 minutes -Alarm Sound once every 6s -Fault Continuous beeping INTERFACE -RS232 Support background software through standard cables -Input IEC C14 IEC C20 -Output 2 National standard sockets 4 National standard sockets 3National standard sockets+1 20A connecting terminal OPTION -SNMP Card Monitor the machine through the network -AS400 Dry Contact Pluggable DB9 dry connector card or phoenix terminal -USB B-type USB port -RS485 RS485 communication interface -EPO Emergency power off External Battery Temperature External battery temperature detection -RJ45 Surge Protection Port Surge Protection -BMS Dry contact for Lithium Battery BMS MECHANICAL -W*D*H(mm) 144*350*224 144*350*224 144*410*223 190*405*330 144*410*223 190*405*330 -W*D*H(mm)(Package size) 238*446*311 238*446*311 244*506*308 280*520*410 244*506*308 280*520*410 -Net weight (KG) 4.3 10.3 5.8 21.1 6.2 25.5 -Gross weight (KG) 5.6 11.6 7.1 23 7.5 27.5 Color Black -
Brochure of HTC11 Series Tower Online UPS 1-3kVA 2.0 (220V230V240V).pdf
Features
Specifications
Certification
Download
● Wide range of input voltage while input PF>0.99
● Output PF of 1, upgraded overload capability
● Full protection of over-voltage and short-circuit
● Multiple communication interface: RS232 RS485AS400, dry contact, USB and SNMP card
● LCD/LED display, monitoring all the operation status
● Auto fan speed adjustment
● External environment and battery temperature sensor
● 1-12A adjustable charger with more flexibility
● Support Lithium battery
HT1101CL | HT1101CS | HT1102CL | HT1102CS | HT1103CL | HT1103CS | |
System Capacity | 1kVA | 2kVA | 3kVA | |||
Phase | Single Phase in, Single Phase out | |||||
Battery Cold Start | Standard | |||||
Input Volatge Range | 110VAC~300VAC | |||||
176VAC~276VAC for 100% load; 276VAC~300VAC for 50% load; 110VAC~176VAC load decrease linearly from 100%~50% | ||||||
Transfer Voltage Range | 220/230/240VAC | |||||
-Line low transfer | 110VAC | |||||
-Line low recovery | 120VAC | |||||
-Line high transfer | 300VAC | |||||
-Line high recovery | 290VAC | |||||
Input Current | ||||||
Rated Current | 4.9A | 9.7A | 14.5A | |||
Input Power Factor | ≥0.99 | |||||
THDi | <3% (100% Linear load); <5% (non-linear load) | |||||
Input frequency Range | 50/60±5Hz(Default),±1Hz/±3Hz(Optional) | |||||
Output | ||||||
Frequency adaptable | Settable | |||||
Power | ||||||
Apparent Power(KVA) | 1 | 2 | 3 | |||
Active Power(KW) | 1(0.9 for 200VAC/208VAC) | 2(1.8 for 200VAC/208VAC) | 3(2.7 for 200VAC/208VAC) | |||
Output Voltage | ||||||
-Waveform(Bat. Mode) | Pure Sine Wave | |||||
Rated Voltage | 220/230/240VAC, 200/208VAC (PF=0.9) | |||||
-Voltage regulation | ± 1 % | |||||
- Dynamic response | ≤5% (0% - 100% -0%) | |||||
- Dynamic recovery | ≤40ms (0% - 100% -0%) | |||||
- Voltage distortion | ≤1% THD,linear load | |||||
≤ 5% THD, non-linear load | ||||||
Output Frequency | ||||||
Synchronization range | Mains mode: follow the mains frequency,Battery mode: 50/60Hz±0.1% | |||||
Transfer Time | ||||||
-Line mode to battery mode | 0 | |||||
-Inverter to bypass | 2ms | |||||
Effciency | ||||||
-Line mode with battery full charged | 94.5%@100% load | 95%@100% load | 95.5%@100% load | |||
-ECO mode | 98.0% | |||||
-Battery mode | 89.5%@100% load | 91.5%@100% load | 91.5%@100% load | |||
Noise(1m away) | <43dB@<60%load,<47dB@>60%load | <50dB@<60%load,<55dB@>60%load | ||||
Overload Capability(Inverter) | 102%~110%: Transfer to bypass after 30mins | |||||
110%~125%: Transfer to bypass after 10mins | ||||||
125%~150%: Transfer to bypass after 30s | ||||||
Overload Capability(Battery Mode) | 102%~110%:Transfer to bypass after 1min | |||||
110%~125%: Transfer to bypass after 10s | ||||||
125%~150%:shutdown after 5s | ||||||
Overload Capability (Bypass Mode) | <130%: Long time | |||||
130%~150%: shutdown after10mins | ||||||
150%~180%: shutdown after 5s | ||||||
Crest Factor | 3:1 | |||||
BATTERY | ||||||
Rating/Type | Depend on the capacity of external batteries | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/7Ah |
Quantity | 3 | 6 | 8 | |||
DC Voltage | 36VDC | 72VDC | 96VDC | |||
Back-up Time | Depend on the capacity of external batteries | 3mins @80% load | Depend on the capacity of external batteries | 3mins @80% load | Depend on the capacity of external batteries | 3mins @80% load |
Battery Charger | ||||||
-Charging Voltage | ||||||
-Charging Current | 1-12A(Settable) | 1A | 1-12A(Settable) | 1A | 1-12A(Settable) | 1A |
- Charging Time | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% |
INDICATOR & ALARM | ||||||
-Display | LED+LCD | |||||
-Discharge | Sound once every 2 minutes | |||||
-Low Battery Voltage | Sound once every 6s | |||||
-Battery Overload | Continuous beeping | |||||
-Input Voltage Abnormality(Include Sequential Negative,Ground wire not connected) | Sound once every 2 minutes | |||||
-Alarm | Sound once every 6s | |||||
-Fault | Continuous beeping | |||||
INTERFACE | ||||||
-RS232 | Support background software through standard cables | |||||
-Input | IEC C14 | IEC C20 | ||||
-Output | 2 National standard sockets | 4 National standard sockets | 3National standard sockets+1 20A connecting terminal | |||
OPTION | ||||||
-SNMP Card | Monitor the machine through the network | |||||
-AS400 Dry Contact | Pluggable DB9 dry connector card or phoenix terminal | |||||
-USB | B-type USB port | |||||
-RS485 | RS485 communication interface | |||||
-EPO | Emergency power off | |||||
External Battery Temperature | External battery temperature detection | |||||
-RJ45 Surge Protection | Port Surge Protection | |||||
-BMS | Dry contact for Lithium Battery BMS | |||||
MECHANICAL | ||||||
-W*D*H(mm) | 144*350*224 | 144*350*224 | 144*410*223 | 190*405*330 | 144*410*223 | 190*405*330 |
-W*D*H(mm)(Package size) | 238*446*311 | 238*446*311 | 244*506*308 | 280*520*410 | 244*506*308 | 280*520*410 |
-Net weight (KG) | 4.3 | 10.3 | 5.8 | 21.1 | 6.2 | 25.5 |
-Gross weight (KG) | 5.6 | 11.6 | 7.1 | 23 | 7.5 | 27.5 |
Color | Black |
Related Application Cases
Related Products
HR31 Series Rack Online UPS 15-20kVA (220V/230V/240V)
The series 3:1 Rack Online UPS is online double-conversion UPS with full DSP control technology. With high input and output power factor, self-adjusting output frequency and network management. The series has 15kVA, 20kVA can be chosen.
HR11 Series Rack Online UPS 1-10kVA (220V/230V/240V)
The series 1:1 Rack Online UPS is the ideal choice for small data center. It supports in-built battery. And the 6kVA and 10kVA rack UPS of this series apply the advanced 3 level of technology, compatible with complicated load. The series has 1kVA, 2kVA, 3kVA, 6kVA, 10 kVA can be chosen.
HT11 Series Tower Online UPS 6-20kVA (220V/230V/240V)
This series tower online UPS contain a standard model with built-in batteries and a long backup model.Smaller size with higher power density, double conversion online UPS with fully DSP controlled technology,this series is a perfect choice for computers, telecommunication equipment and other sensitive devices. The series has 6kVA, 10kVA, 15kVA, 20kVA can be chosen.
HT31 Series Tower Online UPS 10-40kVA (220V/230V/240V)
The series 3:1 Tower Online UPS is double conversion online UPS with fully DSP controlled technology. it provides 12A charger for option, and the digital charger can adjust from 1A to 5A. It’s a perfect choice for computers, telecommunication equipments and other sensitive devices. The series has 10kVA, 15kVA, 20kVA, 40kVA can be chosen.