HT11 Series Tower Online UPS 6-20kVA (220V/230V/240V)
This series single phase tower online UPS contain a standard model with built-in batteries and a long backup model.Smaller size with higher power density, double conversion online UPS with fully DSP controlled technology,this series is a perfect choice for computers, telecommunication equipment and other sensitive devices. The series has 6kVA, 10kVA, 15kVA, 20kVA can be chosen. ( watch the introduction video on YouTube )
Email Us
- Product description
- Features
- Specifications
- Certification
- Download
-
This series single phase tower online UPS contain a standard model with built-in batteries and a long backup model.Smaller size with higher power density, double conversion online UPS with fully DSP controlled technology,this series is a perfect choice for computers, telecommunication equipment and other sensitive devices. The series has 6kVA, 10kVA, 15kVA, 20kVA can be chosen. ( watch the introduction video on YouTube )
-
● High efficiency, up to 95%
● kVA=kW, Output PF=1
● 3 level of technology, compatible with complicated load
● Battery number can be set on LCD
● Intelligent charging management, effectively improving the life time of battery
● Smaller size with higher power density
● Parallel up to 4 units
● 12A charger for option, charging for large capacity batteries
-
HT1106XS HT1106XL HT1110XS HT1110XL INPUT Cold Start YES
Default output frequency will be 50Hz or settableAcceptable Input Voltage 110VAC~288VAC 100% load@>176VAC 90% load@>154VAC 75% load@>132VAC 50% load@>110VAC Phase Single phase in,single phase out Transfer Voltage Range 220VAC/230VAC/240VAC(PF=1) -Line low transfer 110VAC -Line low recovery 121VAC -Line high transfer 288VAC -Line high recovery 281VAC Input Current -Rating(nominal input voltage) 30A/220V 34A/220V 49A/220V 53A/220V Input Power Factor ≥0.99 Input current distortion <4% Input Frequency Range 40~70Hz OUTPUT Frequency adaptable Settable Power -Power 6KVA 10KVA -Power(kW) 6KW 10KW Output Voltage -Waveform(Bat. Mode) Pure Sine Wave -Nominal voltage 220VAC/230VAC/240VAC -Voltage regulation ± 1 % -Voltage distortion ≤1% THD, linear load ≤ 5% THD, non linear load Output Frequency -Synchronization range 50/60 HZ±5Hz default, settable -Battery mode (50±0.1) Hz default Transfer Time -Line mode to battery mode 0ms -Inverter to bypass 0ms Efficiency -Line mode with battery full charged 95%MAX -ECO mode 98.0% Noise(1m away) <58dB Overload Capability(Inverter) 105% to 110% : Transfer to bypass after 10 mins. 111% to 125% : Transfer to bypass after 1 mins. 126% to 150%: Transfer to bypass after 30s Overload Capability (Bypass Mode) less than 125%: long time running 126% to 130% :Shutdown in 5 mins 131% to 150% :Shutdown in 1 mins > 150% :Shutdown in 200 ms Crest Ratio 3:1 BATTERY Rating/Type 12VDC/7Ah Depend on the capacity of external batteries 12VDC/9Ah Depend on the capacity of external batteries Quantity 16PCS default, 20PCS settable 16-20PCS settable 16PCS default, 20PCS settable 16-20PCS settable DC Voltage 192VDC default, settable Back-up Time 4.5mins @80%load Depend on the capacity of external batteries 2.5mins @80%load Depend on the capacity of external batteries Charger -Charging current (max) 1A, settable 5A max,settable 1A,settable 5A max,settable -Float Charging Voltage 2.25V/cell default, setttable via software -Boost Charging Voltage 2.25V/cell default, setttable via software -Charging time 8h recharge to 90% Depend on the capacity of external batteries 8h recharge to 90% Depend on the capacity of external batteries Leakage current <3mA Indicator & Alarm -Display LED+LCD Inteface -Smart RS232 Standard Cable support INVT Power Monitor Software -EPO NC -RS485(option) Installed in the intelligent slot -SNMP(option) Power Managment from SNMP Manager and Web Browser Option -Intelligent Kits DB9 port, dry contact -parallel 4 units paralleled -Super charger (12A) digitally controlled, 4-steps charge, settable,@PF0.9 -USB B-type USB port -SNMP Kits Pluggable type Working Enviroment Mechanical -W╳D╳H (mm) 190*426*705 190*426*336 190*485*705 190*485*336 -Net Weight (KG) 56 14 60 16 -Package Weight (KG) 61 15 70 17 -Rack / Tower Tower Color Black default HT1115XL HT1120XL INPUT Cold Start YES
Default output frequency will be 50Hz or settableAcceptable Input Voltage 110VAC~288VAC 100% load@>176VAC 90% load@>154VAC 75% load@>132VAC 50% load@>110VAC Phase Single phase in,single phase out Transfer Voltage Range 220/230/240VAC -Line low transfer 110VAC -Line low recovery 121VAC -Line high transfer 288VAC -Line high recovery 281VAC Input Current -Rating(nominal input voltage) 25A/380V 33A/380V -Input Power Factor ≥0.99 -Input current distortion ≤4% -Input Frequency Range 40~70Hz OUTPUT Frequency adaptable Settable Power -Power 15KVA 20KVA -Power(kW) 15KW 20KW Output Voltage -Waveform(Bat. Mode) Pure Sine Wave -Nominal voltage L-N 220VAC/230VAC/240VAC, 200VAC/208VAC(PF=0.9) -Voltage regulation ± 1 % -Voltage distortion ≤1% THD, linear load ≤5% THD, non linear load Output Frequency -Synchronization range ±5Hz default, settable -Battery mode (50±0.1) Hz default Transfer Time -Line mode to battery mode 0ms -Inverter to bypass 0ms Efficiency -Line mode with battery full charged 94%@100% load, 94.5%@70% load -ECO mode 98.0% Noise(1m away) <62dB Overload Capability(Inverter) 105% to 110% : Transfer to bypass after 10 mins. 111% to 125% : Transfer to bypass after 1 mins. 126% to 150%: Transfer to bypass after 30s Overload Capability (Bypass Mode) less than 125%: long time running 126% to 130% :Shutdown in 5 mins 131% to 150% :Shutdown in 1 mins > 150% :Shutdown in 200 ms BATTERY Quantity 16-20PCS settable DC Voltage 192VDC default, settable Charger -Charging current (max) 5A max,settable -Float Charging Voltage 2.25V/cell default, setttable via software -Boost Charging Voltage 2.25V/cell default, setttable via software Indicator & Alarm -Display LED+LCD Inteface -Smart RS232 Standard Cable support INVT Power Monitor Software -EPO NC, NO settable, forbidden default -RS485(option) Installed in the intelligent slot -SNMP(option) Power Managment from SNMP Manager and Web Browser Option -Intelligent dry contact DB9 port or terminal -parallel 4 units paralleled -Super charger (12A) digitally controlled, 4-steps charge, settable -USB B-type USB port -SNMP Kits Pluggable type Working Enviroment -storage -40~70℃ -working 0~40℃, huminity 95% non condesation, attitude<1500m (@full load) Mechanical -W╳D╳H (mm) 190*485*480 -Net Weight (KG) 30 -Package Weight (KG) 33 -Rack / Tower Tower Color Black default -
Brochure of HT11 Series Tower Online UPS 6-20kVA (220V230V240V).pdf
Features
Specifications
Certification
Download
● High efficiency, up to 95%
● kVA=kW, Output PF=1
● 3 level of technology, compatible with complicated load
● Battery number can be set on LCD
● Intelligent charging management, effectively improving the life time of battery
● Smaller size with higher power density
● Parallel up to 4 units
● 12A charger for option, charging for large capacity batteries
HT1106XS | HT1106XL | HT1110XS | HT1110XL | |
INPUT | ||||
Cold Start | YES Default output frequency will be 50Hz or settable |
|||
Acceptable Input Voltage | 110VAC~288VAC | |||
100% load@>176VAC | ||||
90% load@>154VAC | ||||
75% load@>132VAC | ||||
50% load@>110VAC | ||||
Phase | Single phase in,single phase out | |||
Transfer Voltage Range | 220VAC/230VAC/240VAC(PF=1) | |||
-Line low transfer | 110VAC | |||
-Line low recovery | 121VAC | |||
-Line high transfer | 288VAC | |||
-Line high recovery | 281VAC | |||
Input Current | ||||
-Rating(nominal input voltage) | 30A/220V | 34A/220V | 49A/220V | 53A/220V |
Input Power Factor | ≥0.99 | |||
Input current distortion | <4% | |||
Input Frequency Range | 40~70Hz | |||
OUTPUT | ||||
Frequency adaptable | Settable | |||
Power | ||||
-Power | 6KVA | 10KVA | ||
-Power(kW) | 6KW | 10KW | ||
Output Voltage | ||||
-Waveform(Bat. Mode) | Pure Sine Wave | |||
-Nominal voltage | 220VAC/230VAC/240VAC | |||
-Voltage regulation | ± 1 % | |||
-Voltage distortion | ≤1% THD, linear load | |||
≤ 5% THD, non linear load | ||||
Output Frequency | ||||
-Synchronization range | 50/60 HZ±5Hz default, settable | |||
-Battery mode | (50±0.1) Hz default | |||
Transfer Time | ||||
-Line mode to battery mode | 0ms | |||
-Inverter to bypass | 0ms | |||
Efficiency | ||||
-Line mode with battery full charged | 95%MAX | |||
-ECO mode | 98.0% | |||
Noise(1m away) | <58dB | |||
Overload Capability(Inverter) | 105% to 110% : Transfer to bypass after 10 mins. | |||
111% to 125% : Transfer to bypass after 1 mins. | ||||
126% to 150%: Transfer to bypass after 30s | ||||
Overload Capability (Bypass Mode) | less than 125%: long time running | |||
126% to 130% :Shutdown in 5 mins | ||||
131% to 150% :Shutdown in 1 mins | ||||
> 150% :Shutdown in 200 ms | ||||
Crest Ratio | 3:1 | |||
BATTERY | ||||
Rating/Type | 12VDC/7Ah | Depend on the capacity of external batteries | 12VDC/9Ah | Depend on the capacity of external batteries |
Quantity | 16PCS default, 20PCS settable | 16-20PCS settable | 16PCS default, 20PCS settable | 16-20PCS settable |
DC Voltage | 192VDC default, settable | |||
Back-up Time | 4.5mins @80%load | Depend on the capacity of external batteries | 2.5mins @80%load | Depend on the capacity of external batteries |
Charger | ||||
-Charging current (max) | 1A, settable | 5A max,settable | 1A,settable | 5A max,settable |
-Float Charging Voltage | 2.25V/cell default, setttable via software | |||
-Boost Charging Voltage | 2.25V/cell default, setttable via software | |||
-Charging time | 8h recharge to 90% | Depend on the capacity of external batteries | 8h recharge to 90% | Depend on the capacity of external batteries |
Leakage current | <3mA | |||
Indicator & Alarm | ||||
-Display | LED+LCD | |||
Inteface | ||||
-Smart RS232 | Standard Cable support INVT Power Monitor Software | |||
-EPO | NC | |||
-RS485(option) | Installed in the intelligent slot | |||
-SNMP(option) | Power Managment from SNMP Manager and Web Browser | |||
Option | ||||
-Intelligent Kits | DB9 port, dry contact | |||
-parallel | 4 units paralleled | |||
-Super charger (12A) | digitally controlled, 4-steps charge, settable,@PF0.9 | |||
-USB | B-type USB port | |||
-SNMP Kits | Pluggable type | |||
Working Enviroment | ||||
Mechanical | ||||
-W╳D╳H (mm) | 190*426*705 | 190*426*336 | 190*485*705 | 190*485*336 |
-Net Weight (KG) | 56 | 14 | 60 | 16 |
-Package Weight (KG) | 61 | 15 | 70 | 17 |
-Rack / Tower | Tower | |||
Color | Black default |
HT1115XL | HT1120XL | |
INPUT | ||
Cold Start | YES Default output frequency will be 50Hz or settable |
|
Acceptable Input Voltage | 110VAC~288VAC | |
100% load@>176VAC | ||
90% load@>154VAC | ||
75% load@>132VAC | ||
50% load@>110VAC | ||
Phase | Single phase in,single phase out | |
Transfer Voltage Range | 220/230/240VAC | |
-Line low transfer | 110VAC | |
-Line low recovery | 121VAC | |
-Line high transfer | 288VAC | |
-Line high recovery | 281VAC | |
Input Current | ||
-Rating(nominal input voltage) | 25A/380V | 33A/380V |
-Input Power Factor | ≥0.99 | |
-Input current distortion | ≤4% | |
-Input Frequency Range | 40~70Hz | |
OUTPUT | ||
Frequency adaptable | Settable | |
Power | ||
-Power | 15KVA | 20KVA |
-Power(kW) | 15KW | 20KW |
Output Voltage | ||
-Waveform(Bat. Mode) | Pure Sine Wave | |
-Nominal voltage | L-N 220VAC/230VAC/240VAC, 200VAC/208VAC(PF=0.9) | |
-Voltage regulation | ± 1 % | |
-Voltage distortion | ≤1% THD, linear load | |
≤5% THD, non linear load | ||
Output Frequency | ||
-Synchronization range | ±5Hz default, settable | |
-Battery mode | (50±0.1) Hz default | |
Transfer Time | ||
-Line mode to battery mode | 0ms | |
-Inverter to bypass | 0ms | |
Efficiency | ||
-Line mode with battery full charged | 94%@100% load, 94.5%@70% load | |
-ECO mode | 98.0% | |
Noise(1m away) | <62dB | |
Overload Capability(Inverter) | 105% to 110% : Transfer to bypass after 10 mins. | |
111% to 125% : Transfer to bypass after 1 mins. | ||
126% to 150%: Transfer to bypass after 30s | ||
Overload Capability (Bypass Mode) | less than 125%: long time running | |
126% to 130% :Shutdown in 5 mins | ||
131% to 150% :Shutdown in 1 mins | ||
> 150% :Shutdown in 200 ms | ||
BATTERY | ||
Quantity | 16-20PCS settable | |
DC Voltage | 192VDC default, settable | |
Charger | ||
-Charging current (max) | 5A max,settable | |
-Float Charging Voltage | 2.25V/cell default, setttable via software | |
-Boost Charging Voltage | 2.25V/cell default, setttable via software | |
Indicator & Alarm | ||
-Display | LED+LCD | |
Inteface | ||
-Smart RS232 | Standard Cable support INVT Power Monitor Software | |
-EPO | NC, NO settable, forbidden default | |
-RS485(option) | Installed in the intelligent slot | |
-SNMP(option) | Power Managment from SNMP Manager and Web Browser | |
Option | ||
-Intelligent dry contact | DB9 port or terminal | |
-parallel | 4 units paralleled | |
-Super charger (12A) | digitally controlled, 4-steps charge, settable | |
-USB | B-type USB port | |
-SNMP Kits | Pluggable type | |
Working Enviroment | ||
-storage | -40~70℃ | |
-working | 0~40℃, huminity 95% non condesation, attitude<1500m (@full load) | |
Mechanical | ||
-W╳D╳H (mm) | 190*485*480 | |
-Net Weight (KG) | 30 | |
-Package Weight (KG) | 33 | |
-Rack / Tower | Tower | |
Color | Black default |
Related Application Cases
Related Products
HR31 Series Rack Online UPS 15-20kVA (220V/230V/240V)
The series 3:1 Rack Online UPS is online double-conversion UPS with full DSP control technology. With high input and output power factor, self-adjusting output frequency and network management. The series has 15kVA, 20kVA can be chosen.
HR11 Series Rack Online UPS 1-10kVA (220V/230V/240V)
The series 1:1 Rack Online UPS is the ideal choice for small data center. It supports in-built battery. And the 6kVA and 10kVA rack UPS of this series apply the advanced 3 level of technology, compatible with complicated load. The series has 1kVA, 2kVA, 3kVA, 6kVA, 10 kVA can be chosen.
HTC11 Series Tower Online UPS 1-3kVA 2.0 (220V/230V/240V)
This series tower UPS is the 2.0 version of HT11 1-3kVA, which is to meet the requirements for energy conservation and emission reduction of the markets, compared with the old one, it has a smaller size, better performance, and more competitive price and quality! its power ranges from 1kVA to 3kVA, This product can be widely used, such as small data centers, bank branches, telecom business halls, office buildings, and various edge computing scenarios.
HT31 Series Tower Online UPS 10-40kVA (220V/230V/240V)
The series 3:1 Tower Online UPS is double conversion online UPS with fully DSP controlled technology. it provides 12A charger for option, and the digital charger can adjust from 1A to 5A. It’s a perfect choice for computers, telecommunication equipments and other sensitive devices. The series has 10kVA, 15kVA, 20kVA, 40kVA can be chosen.