HT33 Series Tower Online UPS 10-40kVA (380V/400V/415V)
The series Tower Online UPS for small load scenarios, and widely used in office, health care equipment and the mall. It has 10kVA, 15kVA, 20kVA, 30kVA, 40kVA can be chosen, and supports 8 units parallel. Otherwise, the 20kVA and 30kVA product can also be used in industrial site, such as ceramic factories, glass factories and other processing industries.
Email Us
- Product description
- Features
- Specifications
- Certification
- Download
-
The series Tower Online UPS for small load scenarios, and widely used in office, health care equipment and the mall. It has 10kVA, 15kVA, 20kVA, 30kVA, 40kVA can be chosen, and supports 8 units parallel. Otherwise, the 20kVA and 30kVA product can also be used in industrial site, such as ceramic factories, glass factories and other processing industries.
-
● High Efficiency,up to 96%
● High input PF>0.99;Input current THDi<3%
● Muti-protection, as temperature, overload, battery under voltage, fan failures, short-circuit
● Four circuit breakers, providing full protection when fault happens battery cold start
● Full DSP control
● Battery management: smart charging control, auto maintenance, greatly extend the battery life
● Parallel up to 8 units
● Friendly operation interface, high-resolution LCD screen
-
Mode HT33010XL HT33010XS HT33015XL HT33015XS HT33020XL HT33020XS HT33030XL HT33030XS HT33040XL HT33040XS Main Input Grid System 3 Phases + Neutral + Ground Rated Input Voltage 380/400/415VAC (Line-Line) Rated Frequency 50/60Hz Input Voltage Range 304~478Vac (Line-Line),full load;
228V~304Vac (Line-Line),load decreases linearly according to the min phase voltageInput Frequency Range 40Hz~70Hz Input Power Factor
>0.99Input Current THDi <4% (full Linear Load) <3% (full Linear Load) Bypass Input Rated Bypass Voltage 380/400/415VAC (Line-Line) Rated Frequency 50/60Hz Bypass Voltage Range Selectable, default -20%~+15%;
Upper limit: +10%, +15%, +20%, +25%;
Lower limit: -10%, -15%, -20%, -30%, -40%Bypass Frequency Range Selectable, ±1Hz, ±3Hz, ±5Hz Bypass Overload 125% Long term operation;
125%~130% for 10min;
130%~150% for 1min;Output Rated Inverter Voltage 380/400/415VAC (Line-Line) Rated Frequency 50/60Hz Output Power Factor 1 0.9 Voltage precision ±1.5%(0-100% linear load) Transient Response <5% for step load (20% - 80% -20%) Transient recovery < 30ms for step load (20% - 100% -20%) Output Voltage THDu <1% (linear load);
<5.5% (non-linear load) according to IEC/EN62040-3<1% linear load;
<6 (non-linear load) according to IEC/EN62040-3Inverter Overload <110%, 60min;
110%~125%,10min;
125%~150%,1min;Frequency Regulation 50/60Hz±0.1% Synchronized Range Settable, ±0.5Hz ~ ±5Hz, default ±3Hz Synchronized Slew Rate Settable, 0.5Hz/S ~ 3Hz/s, default 0.5Hz/s Battery And Charger Battery Rate Voltage ±240VDC Charger Voltage precision 1% Charger Power max=20% System Power Efficiency Normal Operation 95%max >95% >96% Battery Operation 94.5%max >95% >96% System Display LED + LCD Interface Standard: RS232, RS485
Option: SNMP, Dry Contact, Parallel kit,
Battery cold startEnvironmental Operation Temperature 0 ~ 40 ℃ Storage Temperature -40 ~ 70 ℃ Relative Humidity 0 ~ 95% (Non condensing) Noise (1 meter) 58dB @ 100% load, 52dB @ 45% load 65dB @ 100% load, 62dB @ 45% load Physical data Dimension
(W*D*H,mm)250*660*530 250*840*715 250*660*530 250*840*715 250*680*770 350*738*1335 250*680*770 350*738*1335 250*836*770 500*840*1400 Weigh(Kg) 31 51.5
(without battery)31 51.5
(without battery)50 89
(without battery)52 89
(without battery)61 140 -
-
Brochure of HT33 Series Tower Online UPS 10-40kVA (380V400V415V).pdf
Features
Specifications
Certification
Download
● High Efficiency,up to 96%
● High input PF>0.99;Input current THDi<3%
● Muti-protection, as temperature, overload, battery under voltage, fan failures, short-circuit
● Four circuit breakers, providing full protection when fault happens battery cold start
● Full DSP control
● Battery management: smart charging control, auto maintenance, greatly extend the battery life
● Parallel up to 8 units
● Friendly operation interface, high-resolution LCD screen
Mode | HT33010XL | HT33010XS | HT33015XL | HT33015XS | HT33020XL | HT33020XS | HT33030XL | HT33030XS | HT33040XL | HT33040XS |
Main Input | ||||||||||
Grid System | 3 Phases + Neutral + Ground | |||||||||
Rated Input Voltage | 380/400/415VAC (Line-Line) | |||||||||
Rated Frequency | 50/60Hz | |||||||||
Input Voltage Range | 304~478Vac (Line-Line),full load; 228V~304Vac (Line-Line),load decreases linearly according to the min phase voltage |
|||||||||
Input Frequency Range | 40Hz~70Hz | |||||||||
Input Power Factor | >0.99 |
|||||||||
Input Current THDi | <4% (full Linear Load) | <3% (full Linear Load) | ||||||||
Bypass Input | ||||||||||
Rated Bypass Voltage | 380/400/415VAC (Line-Line) | |||||||||
Rated Frequency | 50/60Hz | |||||||||
Bypass Voltage Range | Selectable, default -20%~+15%; Upper limit: +10%, +15%, +20%, +25%; Lower limit: -10%, -15%, -20%, -30%, -40% |
|||||||||
Bypass Frequency Range | Selectable, ±1Hz, ±3Hz, ±5Hz | |||||||||
Bypass Overload | 125% Long term operation; 125%~130% for 10min; 130%~150% for 1min; |
|||||||||
Output | ||||||||||
Rated Inverter Voltage | 380/400/415VAC (Line-Line) | |||||||||
Rated Frequency | 50/60Hz | |||||||||
Output Power Factor | 1 | 0.9 | ||||||||
Voltage precision | ±1.5%(0-100% linear load) | |||||||||
Transient Response | <5% for step load (20% - 80% -20%) | |||||||||
Transient recovery | < 30ms for step load (20% - 100% -20%) | |||||||||
Output Voltage THDu | <1% (linear load); <5.5% (non-linear load) according to IEC/EN62040-3 |
<1% linear load; <6 (non-linear load) according to IEC/EN62040-3 |
||||||||
Inverter Overload | <110%, 60min; 110%~125%,10min; 125%~150%,1min; |
|||||||||
Frequency Regulation | 50/60Hz±0.1% | |||||||||
Synchronized Range | Settable, ±0.5Hz ~ ±5Hz, default ±3Hz | |||||||||
Synchronized Slew Rate | Settable, 0.5Hz/S ~ 3Hz/s, default 0.5Hz/s | |||||||||
Battery And Charger | ||||||||||
Battery Rate Voltage | ±240VDC | |||||||||
Charger Voltage precision | 1% | |||||||||
Charger Power | max=20% System Power | |||||||||
Efficiency | ||||||||||
Normal Operation | 95%max | >95% | >96% | |||||||
Battery Operation | 94.5%max | >95% | >96% | |||||||
System | ||||||||||
Display | LED + LCD | |||||||||
Interface | Standard: RS232, RS485 Option: SNMP, Dry Contact, Parallel kit, Battery cold start |
|||||||||
Environmental | ||||||||||
Operation Temperature | 0 ~ 40 ℃ | |||||||||
Storage Temperature | -40 ~ 70 ℃ | |||||||||
Relative Humidity | 0 ~ 95% (Non condensing) | |||||||||
Noise (1 meter) | 58dB @ 100% load, 52dB @ 45% load | 65dB @ 100% load, 62dB @ 45% load | ||||||||
Physical data | ||||||||||
Dimension (W*D*H,mm) |
250*660*530 | 250*840*715 | 250*660*530 | 250*840*715 | 250*680*770 | 350*738*1335 | 250*680*770 | 350*738*1335 | 250*836*770 | 500*840*1400 |
Weigh(Kg) | 31 | 51.5 (without battery) |
31 | 51.5 (without battery) |
50 | 89 (without battery) |
52 | 89 (without battery) |
61 | 140 |
Related Application Cases
Related Products
HR33 Series Rack Online UPS 30-40kVA (380V/400V/415V)
The HR33 Series Rack-mounted Online UPS adopts online double conversion design, based on DSP full digital control, to provide a stable and uninterrupted power supply for important loads, which can eliminate surges, instantaneous high voltage, instantaneous low voltage, and "Power pollution" such as wire noise and frequency offset, provide customers with high-efficiency and high-power-density power supply guarantees. the UPS can be plugged into the 19-inch standard server cabinet of the micro-module data center. The single cabinet has a capacity of 40kVA/40kW, and the system supports 4 parallel.
HT33 Series Tower Online UPS 60-500kVA (380V/400V/415V)
The series Tower Online UPS is a high stability and scalability product for medium and large data center. The series has 60kVA, 80kVA, 90kVA, 100kVA, 120kVA, 150kVA, 200kVA, 250kVA, 300kVA, 400kVA, 500kVA can be chosen. And it supports swappable, each power module capacity reaches 500kVA in one cabinet but footprint less than 1.45m2.
HT33-TX Series Tower Online UPS 10-40kVA (380V/400V/415V)
The series in-built transformers Tower Online UPS for small load scenarios, and widely used in office, health care equipment and the mall. It has 10kVA, 20kVA, 30kVA, 40kVA can be chosen, It has the same outstanding performance as 10-40kVA Tower Online UPS. the 20kVA and 30kVA product can also be used in industrial site, such as ceramic factories, glass factories and other processing industries. And becasue of the in-built galvanic isolation transformer, it provides more safety for small load scenarios.
HR33 Series Rack Online UPS 10-25 kVA (380V/400V/415V)
The series Rack Online UPS is the ideal choice for modern data center. It has 10kVA, 15kVA, 20kVA, 25kVA can be chosen, The series is double conversion online UPS with fully DSP controlled technology,and it can be configured with 3:3 and 3:1 flexibly.