Model
|
RM100/50X
|
RM200/50X
|
RM300/50X
|
RM500/50X
|
Power Rating
|
100kVA/90kW
|
200kVA/180kW
|
300kVA/270kW
|
500kVA/450kW
|
Main Input |
Grid System
|
3 Phases + Neutral + Ground
|
Rated Input Voltage
|
380/400/415VAC
|
Rated Frequency
|
50/60Hz
|
Input Voltage Range
|
304~478Vac (Line-Line),full load
228V~304Vac (Line-Line),load decrease linearly according to the min phase voltage
|
Input Frequency Range
|
40Hz~70Hz
|
Input Power Factor
|
>0.99
|
Input Current THDi
|
<3% (full Linear Load)
|
Bypass Input |
Rated Bypass Voltage
|
380/400/415VAC (Line-Line)
|
Rated Frequency
|
50/60Hz
|
Bypass Voltage Range
|
Selectable, default -20%~+15%
Up limited: +10%, +15%, +20%, +25%
Down limited: -10%, -15%, -20%, -30%, -40%
|
Bypass Frequency Range
|
Selectable, ±1Hz, ±3Hz, ±5Hz
|
Bypass Overload
|
125%, long time operation
125%< load <130%, last for more than 10 minutes
130%<load<150%,last for more than 1 minutes
>150%, last for more than 300ms
|
110% Long term operation
110%~125% last for more than 5min
125%~150% last for more than 1min
>150% last for more than 1s
|
Output |
Rated Inverter Voltage
|
380/400/415VAC (Line-Line)
|
Rated Frequency
|
50/60Hz
|
Output Power Factor
|
0.9
|
Voltage precision
|
±2%
|
Transient Response
|
<5% for step load (20% - 80% -20%)
|
Transient recovery
|
< 30ms for step load (0% - 100% -0%)
|
Output Voltage THDu
|
<1.5% from 0% to 100% linear load
<6% full non-linear load according to IEC/EN62040-3
|
Inverter Overload
|
<110%, 60min;
110%~125%,10min;
125%~150%,1min;
>150%,200ms
|
Frequency Regulation
|
50/60Hz±0.01%
|
Synchronized Range
|
Settable, ±0.5Hz ~ ±5Hz, default ±3Hz
|
Synchronized Slew Rate
|
Settable, 0.5Hz/S ~ 3Hz/S, default 0.5Hz/S
|
Battery And Charger |
Battery Rate Voltage
|
±240VDC
|
Charger Voltage precision
|
1%
|
Charger Power
|
max=20% *Output power
|
Efficiency |
Normal Operation
|
>96%
|
Battery Operation
|
>96%
|
System |
Display
|
LED + LCD + touch screen
|
Interface
|
RS232, RS485, USB,Programmable dry contact |
RS232, RS485, USB,Programmable dry contact,battery cold start |
Option
|
battery cold start,SNMP,AS400,parallel kit,Lightning protection components,Dust Filter,LBS |
SNMP,AS400,parallel kit,Lightning protection components,Dust Filter,LBS |
Environmental |
Operation Temperature
|
0 ~ 40 ℃
|
Storage Temperature
|
-40 ~ 70 ℃
|
Relative Humidity
|
0 ~ 95% Non condencing
|
Noise (1 meter)
|
65dB @ 100% load, 62dB @ 45% load
|
Altitude
|
<1000m, Load derated 1% per 100m From 1000 ~ 2000m
|
Phisical data |
Cabinet Dimension(W*D*H,mm)
|
600*980*1150
|
650*960*1600
|
650*960*2000
|
1300*1100*2000
|
Cabinet Weigh (kg)
|
210
|
350
|
490
|
900
|