Copyright 2018 © Invt Power System(ShenZhen)Co., Ltd.All Rights Reserved  |   粤ICP备10226515号  Powered by  www.300.cn

Products

>
>
>
>
RML Series Modular Online UPS 15-400kVA (200V/208V/220V)
Page view

RML Series Modular Online UPS 15-400kVA (200V/208V/220V)

没有此类产品
Features
Specifications
Application Case
Summary
Download

Independent LCD for Each Power Module

Each power module has an independent LCD, gives users’ direct overview of status data and alarms in real time.

INVT

 

Friendly Interface

10.4" touch color LCD with comprehensive graphical information of operation, easier for customer to maintenance.

INVT

 

Comprehensive Monitoring Management

In each power module, information of critical components is monitored and displayed in real time, giving customers a view of inner status of the system and providing reminder information for maintenance.

  • Maintenance reminder, running time of capacitors and fans displayed and recorded
  • Comprehensive temperature monitoring for thermal abnormal detection
  • Intelligent battery charger for long battery life

INVT

 

Critical Waveform Recording

UPS can record and save the data of the main parameters automatically when faults happen for further analysis.

  • Can record data information and present as waveform for further analysis
  • Can easily spot the causes of the failures, avoid future similar faults

INVT

 

Smart Sleep

Smart Sleep function can intelligently make some power modules go to sleep when load is relatively low, improving the efficiency of the remaining power modules and saving customers on power and cooling costs.

  • Improving efficiency, reducing power and cooling costs
  • Easy setting with just two steps. Customers can select sleep mode and rotation period
  • Power modules working in rotation, prolong the life time

INVT

 

Self-aging

Self-aging is an advanced function applied in all three phase UPS, Self-aging function can test UPS under different load situation without real load, saving more than 90% of energy.

  • Simulate different load conditions without connecting to any real load, saving more than 90% of energy
  • On site setting supported, easy for factory testing

INVT

 

Programmable Dry Contacts

Programmable dry contacts are available in all DM, RML and DT33 series UPS. Customers can easily expand or modify the definition of each port.

  • Abundant options with three inputs and four outputs, all programmable
  • Easy setting, just pull the drop-down menu and set
  • Compatible with all the DM, RML and DT33 series

INVT

Corresponding parameter set not found, please add it in property template of background

MODEL

RML400/20X

RML200/20X

RML120/20X

RML300/15X

RML150/15X

RM090/15X

Capacity

400kVA/320kW

200kVA/160kW

120kVA/96kW

300kVA/300kW

150kVA/150kW

90kVA/90kW

Power module

PML20X (20kVA/16kW)

PML15X (15kVA/15kW)

INPUT

Phase

3 Phase + Neutral + Ground, 200V/208V/220V (line-line)

 

Voltage range

166-261Vac (line-line), full load;
166-125Vac (line-line), load derated from 100%-75% linearly

Frequency range

40Hz-70Hz

Power factor

>0.99

THDi

THDi<3% @ 100% linear load

OUTPUT

Voltage

200V/208V/220V

Voltage regulation

1.5%

Power factor

0.8

1.0

THDu

THD<1% (linear load), THD<6% (non-linear load)

Crest factor

3:1

Overload capability

110% for 1 hour; 125% for 10 min; 150% for 1 min; >150% for 200ms

BATTERY

Voltage

±120VDC

Charge power precision

±1%

Charge power

20%*System Power

SYSTEM

System efficiency

Normal mode:>93%; ECO mode:>98%; Battery mode:>93%

Display

10.4” color touch screen LCD + LED + Keyboard

IP class

IP20

 

Interface

Standard: RS232, RS485, Dry contacts, USB; Optional: SNMP, Expansion dry contact card

Operation/Storage temperature

0-40/-40-70

Relative humidity

0-95% (non-condensing)

Noise

72dB @ 100% load, 68dB @ 45% load (1 meter away)

65dB @ 100% load, 62dB @ 45% load (1 meter away)

72dB @ 100% load, 68dB @ 45% load
(1 meter away)

65dB @ 100% load, 62dB @ 45% load
(1 meter away)

PHYSICAL

 

Weight(kg)

Cabinet

660

220

165

660

220

165

Power Module

PML20X: 34

PML15X: 32

 

Dimension (W*D*H)
(mm)

Cabinet

2000*1050*2000

600*1100*2000

600*1100*1600

2000*1050*2000

600*1100*2000

600*1100*1600

Power Module

PML20X/ PML15X: 460*790*134

 