1

PRODUCTS

HomeProductsSingle phase UPS / HT11 Series Tower Online UPS 6-10kVA (220V/230V/240V)
  • Product Name: HT11 Series Tower Online UPS 6-10kVA (220V/230V/240V)

Inquiry

  • High efficiency, up to 95% kVA=kW, Output PF=1
  • 3 level of technology, compatible with complicated load
  • Self-aging function
  • Intelligent digital charging management,maximum charger current up to 12A
  • Smaller size with higher power density Parallel up to 8 units
     

 

HT1106XS

HT1106XL

HT1110XS

HT1110XL

INPUT

Cold Start

YES
Default output frequency will be 50Hz or settable

Acceptable Input Voltage

110VAC~288VAC

 

100% load@>176VAC

90% load@>154VAC

75% load@>132VAC

50% load@>110VAC

Phase

Single phase in,single phase out

Transfer Voltage Range 

200VAC/208VAC(0.9), 220VAC/230VAC/240VAC(1)

    -Line low transfer

110VAC

    -Line low recovery

121VAC

    -Line high transfer

288VAC

    -Line high recovery

281VAC

Input Current

    -Rating(nominal input voltage)

30A/220V

34A/220V

49A/220V

53A/220V

Input Power Factor

≥0.99

Input current distortion

<4%

Input Frequency Range

40~70Hz

OUTPUT

Frequency adaptable

Settable

Power

 

    -Power

6KVA

10KVA

    -Power(kW)

6KW

10KW

Output Voltage

 

    -Waveform(Bat. Mode)

Pure Sine Wave

    -Nominal voltage

220VAC/230VAC/240VAC,  200VAC/208VAC(PF=0.9)

    -Voltage regulation

± 1 %

    -Voltage distortion

≤1% THD, linear load        

≤ 5% THD, non linear load

Output Frequency

 

    -Synchronization range

±5Hz default, settable

    -Battery mode

(50±0.1) Hz default

Transfer Time

    -Line mode to battery mode

0ms

    -Inverter to bypass

0ms

Efficiency

    -Line mode with battery full charged

94%@100% load, 94.5%@60% load

94.6%@100% load, 95%@60% load

    -ECO mode

99.0%

Noise(1m away)

 <58dB

Overload Capability(Inverter)

105% to 110% : Transfer to bypass after 10 mins.

111% to 125% : Transfer to bypass after 1 mins.

126% to 150%: Transfer to bypass after 30s

Overload Capability (Bypass Mode)

less than 125%: long time running

 126% to 130% :Shutdown in 5 mins

 131% to 150% :Shutdown in 1 mins

> 150%  :Shutdown in 200 ms

Crest Ratio

3:1

BATTERY

Rating/Type

12VDC/7Ah

Depend on the capacity of external batteries

12VDC/9Ah

Depend on the capacity of external batteries

Quantity

16PCS default, 20PCS settable

16-24PCS settable

16PCS default, 20PCS settable

16-24PCS settable

DC Voltage

192VDC default, settable

Back-up Time

3mins @5kW

Depend on the capacity of external batteries

2mins @8kW

Depend on the capacity of external batteries

Charger

    -Charging current (max)

1A, settable

5A max,settable

1A,settable

5A max,settable

    -Float Charging Voltage

2.25V/cell default, setttable via software

    -Boost Charging Voltage

2.25V/cell default, setttable via software

    -Charging time

8h recharge to 90%

Depend on the capacity of external batteries

8h recharge to 90%

Depend on the capacity of external batteries

Leakage current

<3mA

Indicator & Alarm

    -Display

LED+LCD

Inteface

    -Smart RS232

Standard Cable support INVT Power Monitor Software

    -EPO

NC

    -RS485(option)

Installed in the intelligent slot

    -SNMP(option)

Power Managment from SNMP Manager and Web Browser

Option

    -Intelligent Kits

DB9 port, dry contact

    -parallel

4 units paralleled

    -Super charger (12A)

digitally controlled, 4-steps charge, settable

    -USB

B-type USB port

    -SNMP Kits

Pluggable type

Mechanical

    -W╳D╳H (mm)

190*426*705

 190*426*336

190*485*705

190*485*336

    -Net Weight (KG)

56

14

60

16

    -Package Weight (KG)

60

16

65

18

    -Rack / Tower

Tower

Color

 

 

 

 

 

FUNCTION

Compatible with half wave load

 

Main input breaker

Bypass input breaker

ECO mode

Battery cabinet

Self aging

Digital Charger

Remained Battery Capacity

HT11 series, ranging from 6KVA to 10KVA, is double conversion online UPS with fully DSP controlled technology. The single phase UPS applies the advanced 3-level technology, achieving a efficiency up to 95%. With its compact design of high power density (kW=kVA), HT11 series make it ideal choice for computers, telecommunication equipment and other sensitive devices.

Download Attachments: